Fan coil, cassette, for mounting to the suspended ceiling, hygienic version for premises with strict European VDI 6022 standard rules for heating, ventilation and air-conditioning (HVAC) systems, higher frame allows condensate to drain naturally under influence of gravity - no condensate pump is required, EC type ebm‑papst fan, data is provided for the fan operating at three speeds at 2/6/10 V, stainless steel (AISI 304) casing insulated with anti-condensation and sound-absorbing aluminum coated material, G3 class air filter with mesh and frame made entirely of aluminum, diffuser made of sheet metal and painted in RAL9003 white color, heating capacity is calculated at 50°C water and 20°C air temperature, cooling capacity at 7/12°C water and 27°C air temperature, 2 pipe connection, 2.43/5.46/8.60 kW sildīšanas jauda vai 2.17/4.74/7.29 kW dzesēšanas jauda 4 rindu siltummainī, gaisa plūsma 250/590/980 m³/h, skaņas spiediena līmenis 18/34/48 dB(A), maks. ventilatora jauda 45 W, griestu atvere 600x600xH400 mm, svars 20 kg, GARANTIJA 2 gadi
Vai jūs interesē šis produkts? Sazinieties ar mums:

Andrejs Policans

LV, RU, EN
+371 209 26663

Tirdzniecības pārstāvis Latvijā Saņemt piedāvājumu
Noklikšķiniet uz modeļa: parādīsies tehniskā informācija, izmēri, piederumi
PS-CLEI 2T - cassette, for mounting to the suspended ceiling, hygienic version for premises with strict European VDI 6022 standard rules for heating, ventilation and air-conditioning (HVAC) systems, higher frame allows condensate to drain naturally under influence of gravity - no condensate pump is required, EC type ebm‑papst fan, data is provided for the fan operating at three speeds at 2/6/10 V, stainless steel (AISI 304) casing insulated with anti-condensation and sound-absorbing aluminum coated material, G3 class air filter with mesh and frame made entirely of aluminum, diffuser made of sheet metal and painted in RAL9003 white color, heating capacity is calculated at 50°C water and 20°C air temperature, cooling capacity at 7/12°C water and 27°C air temperature, 2 pipe connection
PS-CLEI 2T 070/2R 1.94/3.96/5.85 kW sildīšanas jauda vai 1.27/2.88/4.32 kW dzesēšanas jauda 2 rindu siltummainī, gaisa plūsma 250/590/980 m³/h, skaņas spiediena līmenis 18/34/48 dB(A), maks. ventilatora jauda 41 W, griestu atvere 600x600xH400 mm, svars 18 kg, GARANTIJA 2 gadi
PS-CLEI 2T 070/2R
1.94/3.96/5.85 kW sildīšanas jauda vai 1.27/2.88/4.32 kW dzesēšanas jauda 2 rindu siltummainī, gaisa plūsma 250/590/980 m³/h, skaņas spiediena līmenis 18/34/48 dB(A), maks. ventilatora jauda 41 W, griestu atvere 600x600xH400 mm, svars 18 kg, GARANTIJA 2 gadi
PS-CLEI 2T 090/3R 2.29/4.90/7.47 kW sildīšanas jauda vai 1.89/4.01/6.07 kW dzesēšanas jauda 3 rindu siltummainī, gaisa plūsma 250/590/980 m³/h, skaņas spiediena līmenis 18/34/48 dB(A), maks. ventilatora jauda 45 W, griestu atvere 600x600xH400 mm, svars 19 kg, GARANTIJA 2 gadi
PS-CLEI 2T 090/3R
2.29/4.90/7.47 kW sildīšanas jauda vai 1.89/4.01/6.07 kW dzesēšanas jauda 3 rindu siltummainī, gaisa plūsma 250/590/980 m³/h, skaņas spiediena līmenis 18/34/48 dB(A), maks. ventilatora jauda 45 W, griestu atvere 600x600xH400 mm, svars 19 kg, GARANTIJA 2 gadi
PS-CLEI 2T 090/4R 2.43/5.46/8.60 kW sildīšanas jauda vai 2.17/4.74/7.29 kW dzesēšanas jauda 4 rindu siltummainī, gaisa plūsma 250/590/980 m³/h, skaņas spiediena līmenis 18/34/48 dB(A), maks. ventilatora jauda 45 W, griestu atvere 600x600xH400 mm, svars 20 kg, GARANTIJA 2 gadi
PS-CLEI 2T 090/4R
2.43/5.46/8.60 kW sildīšanas jauda vai 2.17/4.74/7.29 kW dzesēšanas jauda 4 rindu siltummainī, gaisa plūsma 250/590/980 m³/h, skaņas spiediena līmenis 18/34/48 dB(A), maks. ventilatora jauda 45 W, griestu atvere 600x600xH400 mm, svars 20 kg, GARANTIJA 2 gadi
PS-CLEI 4T - cassette, for mounting to the suspended ceiling, hygienic version for premises with strict European VDI 6022 standard rules for heating, ventilation and air-conditioning (HVAC) systems, higher frame allows condensate to drain naturally under influence of gravity - no condensate pump is required, EC type ebm‑papst fan, data is provided for the fan operating at three speeds at 2/6/10 V, stainless steel (AISI 304) casing insulated with anti-condensation and sound-absorbing aluminum coated material, G3 class air filter with mesh and frame made entirely of aluminum, diffuser made of sheet metal and painted in RAL9003 white color, heating capacity is calculated at 50°C water and 20°C air temperature, cooling capacity at 7/12°C water and 27°C air temperature, 4 pipe connection
PS-CLEI 4T 094/2R+1 2.73/5.08/7.19 kW sildīšanas jauda 1 rindas siltummainī vai 1.58/3.30/4.82 kW dzesēšanas jauda 2 rindu siltummainī, gaisa plūsma 250/590/980 m³/h, skaņas spiediena līmenis 18/34/48 dB(A), maks. ventilatora jauda 45 W, griestu atvere 600x600xH400 mm, svars 19.5 kg, GARANTIJA 2 gadi
PS-CLEI 4T 094/2R+1
2.73/5.08/7.19 kW sildīšanas jauda 1 rindas siltummainī vai 1.58/3.30/4.82 kW dzesēšanas jauda 2 rindu siltummainī, gaisa plūsma 250/590/980 m³/h, skaņas spiediena līmenis 18/34/48 dB(A), maks. ventilatora jauda 45 W, griestu atvere 600x600xH400 mm, svars 19.5 kg, GARANTIJA 2 gadi
PS-CLEI 4T 094/3R+1 2.73/5.08/7.19 kW sildīšanas jauda 1 rindas siltummainī vai 2.05/4.26/6.39 kW dzesēšanas jauda 3 rindu siltummainī, gaisa plūsma 250/590/980 m³/h, skaņas spiediena līmenis 18/34/48 dB(A), maks. ventilatora jauda 45 W, griestu atvere 600x600xH400 mm, svars 20.5 kg, GARANTIJA 2 gadi
PS-CLEI 4T 094/3R+1
2.73/5.08/7.19 kW sildīšanas jauda 1 rindas siltummainī vai 2.05/4.26/6.39 kW dzesēšanas jauda 3 rindu siltummainī, gaisa plūsma 250/590/980 m³/h, skaņas spiediena līmenis 18/34/48 dB(A), maks. ventilatora jauda 45 W, griestu atvere 600x600xH400 mm, svars 20.5 kg, GARANTIJA 2 gadi
PS-CLEI hygienic version of cassette fan coil units
Manuals 1.3 MB
Katalogi 671 KB
TEL wireless remote control panel
Manuals 254 KB
Fan coils controllers
Bukleti 8.1 MB
Modelis: PS-CLEI 2T 090/4R
Control panels for fan coils
TER.EC.ANA Control panel, suitable for 2-pipe and 4-pipe units with EC fans, manual 3 steps fan speed selection, integrated thermostat, manual summer/winter mode, on/off valves control, possibility to connect remote air sensor SM, for use with PS-WLE, PS-FSE, PS-FLE/FLEF/FLEH, PS-CLE/CLES/CLEH/CLEHS/CLEI, PS-UWLE/UWLEF/UWLEV/UWLES/UWLED, PS-DCE/HDCE units
TER.EC.ANA
Control panel, suitable for 2-pipe and 4-pipe units with EC fans, manual 3 steps fan speed selection, integrated thermostat, manual summer/winter mode, on/off valves control, possibility to connect remote air sensor SM, for use with PS-WLE, PS-FSE, PS-FLE/FLEF/FLEH, PS-CLE/CLES/CLEH/CLEHS/CLEI, PS-UWLE/UWLEF/UWLEV/UWLES/UWLED, PS-DCE/HDCE units
TER.EC.DIG Control panel, suitable for 2-pipe and 4-pipe units with EC fans, LCD display, manual and automatic 3 steps fan speed selection, integrated thermostat, automatic summer/winter mode if used with optional SM sensor, possibility to remotely turn device on/off, possibility to control additional electric heater, on/off valves control, 0-10V modulating valves control, possibility to connect remote air sensor SM, possibility to connect supply hot water detection temperature sensor TM, for use with PS-WLE, PS-FSE, PS-FLE/FLEF/FLEH, PS-CLE/CLES/CLEH/CLEHS/CLEI, PS-UWLE/UWLEF/UWLEV/UWLES/UWLED, PS-DCE/HDCE units
TER.EC.DIG
Control panel, suitable for 2-pipe and 4-pipe units with EC fans, LCD display, manual and automatic 3 steps fan speed selection, integrated thermostat, automatic summer/winter mode if used with optional SM sensor, possibility to remotely turn device on/off, possibility to control additional electric heater, on/off valves control, 0-10V modulating valves control, possibility to connect remote air sensor SM, possibility to connect supply hot water detection temperature sensor TM, for use with PS-WLE, PS-FSE, PS-FLE/FLEF/FLEH, PS-CLE/CLES/CLEH/CLEHS/CLEI, PS-UWLE/UWLEF/UWLEV/UWLES/UWLED, PS-DCE/HDCE units
TER.EC.BUS Control panel, suitable for 2-pipe and 4-pipe units with EC fans, LCD display, manual and automatic 3 steps fan speed selection, integrated thermostat, automatic summer/winter mode if used with optional TM sensor, programmable weekly calendar, possibility to remotely turn device on/off, possibility to control additional electric heater, on/off valves control, 0-10V modulating valves control, possibility to connect remote air sensor SA, possibility to connect supply hot water detection temperature sensor TM, RS485 connection to BMS via Modbus RTU protocol, for use with PS-WLE, PS-FSE, PS-FLE/FLEF/FLEH, PS-CLE/CLES/CLEH/CLEHS/CLEI, PS-UWLE/UWLEF/UWLEV/UWLES/UWLED, PS-DCE/HDCE units
TER.EC.BUS
Control panel, suitable for 2-pipe and 4-pipe units with EC fans, LCD display, manual and automatic 3 steps fan speed selection, integrated thermostat, automatic summer/winter mode if used with optional TM sensor, programmable weekly calendar, possibility to remotely turn device on/off, possibility to control additional electric heater, on/off valves control, 0-10V modulating valves control, possibility to connect remote air sensor SA, possibility to connect supply hot water detection temperature sensor TM, RS485 connection to BMS via Modbus RTU protocol, for use with PS-WLE, PS-FSE, PS-FLE/FLEF/FLEH, PS-CLE/CLES/CLEH/CLEHS/CLEI, PS-UWLE/UWLEF/UWLEV/UWLES/UWLED, PS-DCE/HDCE units
TER.EC.BAC Control panel, suitable for 2-pipe and 4-pipe units with EC fans, LCD display, manual and automatic 3 steps fan speed selection, integrated thermostat, automatic summer/winter mode if used with optional TM sensor, programmable weekly calendar, possibility to remotely turn device on/off, possibility to control additional electric heater, on/off valves control, 0-10V modulating valves control, possibility to connect remote air sensor SA, possibility to connect supply hot water detection temperature sensor TM, RS485 connection to BMS via BACnet MS/TP protocol, for use with PS-FSE, PS-FLE/FLEF/FLEH, PS-CLE/CLES/CLEH/CLEHS/CLEI, PS-UWLE/UWLEF/UWLEV/UWLES, PS-DCE/HDCE units
TER.EC.BAC
Control panel, suitable for 2-pipe and 4-pipe units with EC fans, LCD display, manual and automatic 3 steps fan speed selection, integrated thermostat, automatic summer/winter mode if used with optional TM sensor, programmable weekly calendar, possibility to remotely turn device on/off, possibility to control additional electric heater, on/off valves control, 0-10V modulating valves control, possibility to connect remote air sensor SA, possibility to connect supply hot water detection temperature sensor TM, RS485 connection to BMS via BACnet MS/TP protocol, for use with PS-FSE, PS-FLE/FLEF/FLEH, PS-CLE/CLES/CLEH/CLEHS/CLEI, PS-UWLE/UWLEF/UWLEV/UWLES, PS-DCE/HDCE units
TER.EC.TOUCH Control panel, suitable for 2-pipe units with EC fans, touch screen, manual and automatic 3 steps fan speed selection, integrated thermostat, manual summer/winter mode, programmable weekly calendar, on/off valves control, possibility to connect remote air sensor SM, Wi-Fi connection for possibility to control the device remotely through the app for smart Android / IOS devices, for use with PS-WLE, PS-FSE, PS-FLE/FLEF/FLEH 2T, PS-CLE/CLES/CLEH/CLEHS/CLEI 2T, PS-UWLE/UWLEF/UWLEV/UWLES/UWLED 2T, PS-DCE/HDCE 2T units
TER.EC.TOUCH
Control panel, suitable for 2-pipe units with EC fans, touch screen, manual and automatic 3 steps fan speed selection, integrated thermostat, manual summer/winter mode, programmable weekly calendar, on/off valves control, possibility to connect remote air sensor SM, Wi-Fi connection for possibility to control the device remotely through the app for smart Android / IOS devices, for use with PS-WLE, PS-FSE, PS-FLE/FLEF/FLEH 2T, PS-CLE/CLES/CLEH/CLEHS/CLEI 2T, PS-UWLE/UWLEF/UWLEV/UWLES/UWLED 2T, PS-DCE/HDCE 2T units
TEL Wireless control panel, suitable for 2-pipe and 4-pipe units, LCD display, manual and automatic 3 steps fan speed selection, manual summer/winter mode, on/off valves control, possibility to connect supply hot water detection temperature sensor TM, for use with PS-CL/CLE/CLES/CLH/CLEH/CLEHS/CLEI, PS-UWL/UWLF/UWLV/UWLE/UWLEF/UWLEV/UWLES, PS-DC/DCE/HDC/HDCE units, required to use together with KIT.TEL or KIT.TEL.EC accessory
TEL
Wireless control panel, suitable for 2-pipe and 4-pipe units, LCD display, manual and automatic 3 steps fan speed selection, manual summer/winter mode, on/off valves control, possibility to connect supply hot water detection temperature sensor TM, for use with PS-CL/CLE/CLES/CLH/CLEH/CLEHS/CLEI, PS-UWL/UWLF/UWLV/UWLE/UWLEF/UWLEV/UWLES, PS-DC/DCE/HDC/HDCE units, required to use together with KIT.TEL or KIT.TEL.EC accessory
Accessories for fan coils controls
KIT.TEL.EC Wireless control panel signal receiver and PCB together with temperature probe, for installation inside fan coil unit with EC type fan, fits to PS-CLE/CLES/CLEH/CLEI, PS-UWLE/UWLEF/UWLEV/UWLES, PS-DCE/HDCE units
KIT.TEL.EC
Wireless control panel signal receiver and PCB together with temperature probe, for installation inside fan coil unit with EC type fan, fits to PS-CLE/CLES/CLEH/CLEI, PS-UWLE/UWLEF/UWLEV/UWLES, PS-DCE/HDCE units
KIT.BUS Electronic board for PS-CLE/CLES/CLEH/CLEI, PS-UWLE/UWLEF/UWLEV/UWLES/UWLED, PS-DCE/HDCE fan coil units with EC fans connection to BMS via Modbus protocol, delivered with air temperature probe
KIT.BUS
Electronic board for PS-CLE/CLES/CLEH/CLEI, PS-UWLE/UWLEF/UWLEV/UWLES/UWLED, PS-DCE/HDCE fan coil units with EC fans connection to BMS via Modbus protocol, delivered with air temperature probe
DIS.BUS Information screen to display data from device controlled via KIT.BUS electronic board
DIS.BUS
Information screen to display data from device controlled via KIT.BUS electronic board
SM Temperature sensor for automatic summer/winter mode change-over in TER.DIG.S / TER.EC.DIG control panels (to be used with units without valve or with 3-way valve), it also can be used as a remote air temperature sensor for TER.ANA(.M) / TER.ANA.S(.M) / TER.EC.ANA(.M) / TER.DIG(.M) / TER.DIG.S / TER.EC.DIG(.M) / TER.BUS(.M) / TER.BAC(.M) / TER.EC.BUS(.M) / TER.EC.BAC / TER.TOUCH(.M) / TER.EC.TOUCH(.M) control panels
SM
Temperature sensor for automatic summer/winter mode change-over in TER.DIG.S / TER.EC.DIG control panels (to be used with units without valve or with 3-way valve), it also can be used as a remote air temperature sensor for TER.ANA(.M) / TER.ANA.S(.M) / TER.EC.ANA(.M) / TER.DIG(.M) / TER.DIG.S / TER.EC.DIG(.M) / TER.BUS(.M) / TER.BAC(.M) / TER.EC.BUS(.M) / TER.EC.BAC / TER.TOUCH(.M) / TER.EC.TOUCH(.M) control panels
TM Supply hot water detection (35°C) temperature sensor for turning on fan coil unit in heating mode only when hot water is flowing, to be used with units without valve or with 3-way valve, usable with TER.ANA.S / TER.ANA.S.M / TER.DIG.S / TER.EC.DIG / TER.EC.DIG.M / TER.BUS / TER.BUS.M / TER.BAC / TER.BAC.M / TER.EC.BUS / TER.EC.BUS.M / TER.EC.BAC / TEL control panels
TM
Supply hot water detection (35°C) temperature sensor for turning on fan coil unit in heating mode only when hot water is flowing, to be used with units without valve or with 3-way valve, usable with TER.ANA.S / TER.ANA.S.M / TER.DIG.S / TER.EC.DIG / TER.EC.DIG.M / TER.BUS / TER.BUS.M / TER.BAC / TER.BAC.M / TER.EC.BUS / TER.EC.BUS.M / TER.EC.BAC / TEL control panels
Water valves
ATT.230 On/Off actuator for water valve, powered by 230 V
ATT.230
On/Off actuator for water valve, powered by 230 V
ATT.230.M On/Off actuator for water valve, powered by 230 V, with limit switch
ATT.230.M
On/Off actuator for water valve, powered by 230 V, with limit switch
ATT.MOD Modulating by 0-10 V signal actuator for water valve
ATT.MOD
Modulating by 0-10 V signal actuator for water valve
VAL.2V.34.CL 2-way water valve for PS-CL/CLE/CLES/CLH/CLEH/CLEI/CLQ fan coil units, 3/4" connection
VAL.2V.34.CL
2-way water valve for PS-CL/CLE/CLES/CLH/CLEH/CLEI/CLQ fan coil units, 3/4" connection
VAL.3V.34.CL 3-way water valve for PS-CL/CLE/CLES/CLH/CLEH/CLEI/CLQ fan coil units, 3/4" connection
VAL.3V.34.CL
3-way water valve for PS-CL/CLE/CLES/CLH/CLEH/CLEI/CLQ fan coil units, 3/4" connection
VAL.DIN.P.34.CL Balancing water valve for PS-CL/CLE/CLES/CLH/CLEH/CLEI fan coil units, 3/4" connection
VAL.DIN.P.34.CL
Balancing water valve for PS-CL/CLE/CLES/CLH/CLEH/CLEI fan coil units, 3/4" connection
Condensate collection trays
BAC.VAL1 Auxiliary drain pan for valve of PS-CL/CLE/CLES/CLH/CLEH/CLEHS/CLEI/CLQ fan coil units
BAC.VAL1
Auxiliary drain pan for valve of PS-CL/CLE/CLES/CLH/CLEH/CLEHS/CLEI/CLQ fan coil units
Additional accessories for fan coils air inlet and outlet
FL.RIN Fresh air inlet flange for PS-CL/CLE/CLES/CLH/CLEH/CLEI/CLQ fan coil units
FL.RIN
Fresh air inlet flange for PS-CL/CLE/CLES/CLH/CLEH/CLEI/CLQ fan coil units
FL.AIR Flange for air supply to the adjacent room, fits PS-CL/CLE/CLES/CLH/CLEH/CLEI/CLQ fan coil units
FL.AIR
Flange for air supply to the adjacent room, fits PS-CL/CLE/CLES/CLH/CLEH/CLEI/CLQ fan coil units
Electric heating elements
KIT.RES.050 1.5 kW power electric heating element for 050 - 094 size PS-CL/CLE/CLES/CLH/CLEH/CLEI fan coil units
KIT.RES.050
1.5 kW power electric heating element for 050 - 094 size PS-CL/CLE/CLES/CLH/CLEH/CLEI fan coil units
Painting in non-standard colors
PAN.MET.RAL.050 Painting of metal diffuser in non-standard RAL color for 050 - 094 size PS-CL/CLE/CLES/CLH/CLEH fan coil units
PAN.MET.RAL.050
Painting of metal diffuser in non-standard RAL color for 050 - 094 size PS-CL/CLE/CLES/CLH/CLEH fan coil units